WIC1g2

Self-powered protection relay

Speed, reinvented.

Self-Powered device

No auxiliary power needed. The WIC1 relays harvest the

required supply energy from the current measurement signals.

Dual-Powered variant

A dual (redundant) powered variant is available in order to enable e.g. communication(#) and early ground (earth) fault detection.

Ultra Fast Boot-uptime

With a start-up time of less than 1 cycle, the WIC1 already protects your equipment whilst other devices are still booting. What if someone is switching onto a fault although the system is still grounded during maintenance? The WIC1 will issue a trip signal almost immediately.

Individual
parameterization

With the WIC1 g2, you have all the options to configure the system according to your individual requirements. Conveniently via the „Smart view“ software (Smart view is the free software by SEG Electronics for easy configuration and evaluation), via DiggiMEC, or traditionally manually via DIP/HEX switches.

DIP / HEX Variants,
for manual Individual
parameterization

With the WIC1 g2, you have all the options to configure the system according to your individual requirements. Conveniently via the „Smart view“ software (Smart view is the free software by SEG Electronics for easy configuration and evaluation), via DiggiMEC, or traditionally manually via DIP/HEX switches.

Communication

The WIC1‑4 features the Modbus RTU protocol via RS485 interface, or Modbus TCP via electrical or optical Ethernet.

Retrofit - No Drilling,
no Sawing

The WIC1 has the same form-factor as the predecessor. You can mount it into the cabinet in just a few minutes. No cabinet needs to be redesigned. No drilling, no sawing will be necessary. You can re-use the previously installed WIC1 CTs: Just switch over the connection cables. The first DIP switch blocks (WIC1-2) / HEX switches (WIC1-3) have the same function as the first WIC1 version, so that the settings are quickly copied.

The new WIC1 g2 -

Ultra fast.

Ultra safe.

Ultra reliable.

The new WIC1 g2 -
Ultra fast. Ultra safe.
Ultra reliable.

The WIC1 family is a series of self-powered / CT powered protection relays, designed for harshest environments. The WIC relay family does not need auxiliary energy since they are CT powered. A dual/redundant powered variant enables communication options in addition to the power outage safe protection core. The main applications are:

  • Protection of Ring Main Units for Power Distribution
  • Protection of Step-Up Transformers e.g. for Wind and Solar Power
  • Protection of Feeders
  • Current based protection when auxiliary power is not available or too costly
  • Backup Protection – available in absence of auxiliary power
  • Disaster recovery – Blackstart capability after (short or long lasting) outages – reliable protection, when other protection relays fail because of drained battery rooms

More great features

  • Super fast and easy mounting
  • Super fast and easy setting
  • Made for Harsh Environment: It is no problem for the WIC1 if the RMU / Transformer is in an area with harsh climate, for example high humidity all the year, or an average temperature above 50°C.
  • Ground Current: The WIC1 offers calculated and measured 1 A ground Current (option).
  • Tripping Characteristics: For inverse-time overcurrent protection, you can select out of 12 characteristics (ground overcurrent: 13)

Four variants -
all possibilities.

Four WIC1 g2 device variants are available to meet a wide range of requirements. For example, the device variants with DIP or HEX switches allow for manual configuration.

The optional DiggiMEC® interface device enables configuration of all device variants via the integrated LCD display and switches, providing access to extended setting ranges and additional protection functions. The DiggiMEC® also allows the WIC to be connected to a Windows PC via USB-C, so the SEG configuration and analysis software „Smart view“ can be used to easily and conveniently configure the WIC1 or to transfer measurement and fault data from the WIC1.

A self-powered WIC1 variant is also available, which additionally supports SCADA communication.

WIC1-1

Base

WIC1-2

DIP

WIC1-3

HEX

WIC1-4

Dual-Powered

System Functional Overview

The WIC1 is a CT-powered protection relay with minimal space requirement (125 x 170 mm), that complies with the highest demands on a digital protection device. Simple but safe wiring, high electromagnetic interference immunity, uncomplicated adjustment and the ability to scale to different power quantities of the switchboard, helping the switchgear manufacturer to

minimize costs. System Overview:

Additional System Components

The WIC1 g2 is optimized for operation with specially designed, highly efficient CTs developed by SEG. If the use of 1 A (or 5 A) standard CTs is mandatory (for technical or historical reasons) it is possible to connect via the SEG PC4 adapter CTs between the 1 A CTs and the WIC1. Below is an overview of the available optional components:

  • Optional DiggiMEC® Nano HMI [for more info about the DiggiMEC® click here]
  • WIC1 wide range CT [Image: 1]
  • PC4 Adapter [Image: 2]
  • Flag indicators [SEG offers two mechanical flag indicators – WI1SZ4 and WI1SZ5 – as accessories for the WIC1. With the DiggiMEC®, there are also up to three flag indicators available.]
  • SEG configuration and analysis software „Smart view“ [Image: 3]

If the DiggiMEC® user interface is connected to the WIC1, it is also possible to connect a PC to the USB interface of the DiggiMEC®. Via PC you can then simply and conveniently execute the parameterizing and analyzing software „Smart view“ and enable the user to make all settings via this connection, or to save settings to a file on the PC, or retrieve measured values or trip event data. Scroll down to find out more about the great features of the new SEG self-powered protection relay. Or do you like to contact our Sales Team regarding any questions?

DiggiMEC® - Nano-HMI with up to three integrated mechanical flag indicators

The DiggiMEC® is an upgrade option to the WIC1 family, It fits into a standard door cutout of 92 mm × 45 mm [DIN IEC 61554]. Its display can visualize measuring values on site. Moreover, the DiggiMEC® provides access to the protection parameters that are always exclusively inside the WIC relay. The Nano-HMI offers integrated Flag Indicators and configurable LEDs and can be mounted in no time and without any drilling.

Software settings (offline created) can be loaded into the WIC1 relays via the USB-C port of the DiggiMEC®. Just connect the DiggiMEC® and WIC1 relay via a standard Ethernet cable.

Settings via DiggiMEC®

Setting of protective elements beyond DIP/HEX switches

  • Alternative Flag Indicator Assignments
  • I>>> (Third Overcurrent Element)
  • IG>> (Second Ground Current Element)
  • Thermal Protection
  • Option for flexible use of the FI (flag indicator) output of the WIC1, e. g. for measuring alarm times, or as a watchdog output (with external DIN rail output relay)

Condition Monitoring

  • Breaker Wear
  • Live Measurement Values Transformer Life Load Monitoring
  • Peak Current Pointer

Commissioning Support

  • Force manually relay positions
  • Trip Indicators (manual reset option)
  • Test Trip (powered via USB)

Auto Fault Report

  • Information comes to you: Fault reports will pop up on the display automatically.
  • Mechanical Flag Indicators indicate in a power outage safe manner what has happened.

Three function packages - for maximum flexibility.

To meet various requirements, we offer three function packages to choose from: „Standard,“ „Advanced,“ or „Professional.“

See this overview for the functions included in each package. For pricing, please contact our sales team directly. We look forward to providing you with a quote.

WIC1-1

WIC1-2

WIC1-3

WIC1-4

Function package

Standard

Function package

Advanced

Function package

Professional

Function Name
IEC
IEEE Device No
Phase Overcurrent Protection
I>
50,51
Phase Overcurrent Protection
I>>
50,51
Phase Overcurrent Protection
I>>>
50,51
Earth (Ground/Neutral) Overcurrent Protection
IG>
50N/G; 51N/G
Earth (Ground/Neutral) Overcurrent Protection
IG>>
50N/G; 51N/G
Station Battery Monitoring
SBM
(only WIC1-4)
External Protection (external Trip)
ExP[1]
Inrush Blocking
IH2
Fault Simulator
Sgen
Circuit Breaker Failure Protection
CBF
50BF
62BF (only WIC1-4)
Trip circuit monitoring
TCM
74TC
Unbalanced Load Protection
I2/I1>
46
Negative Sequence Current Protection
I2>
51Q
Thermal Overload Protection
ThR
49
Breaker Wear Monitoring
BkrWear
Life Load Monitoring
LifeLoad
Peak Overcurrent Protection
Ipeak>
Switch onto Fault Protection
SOTF
Cold Load Pickup
CLPU
External Protection (external Trip)
ExP[2]
(only WIC1-4)

Do you have questions regarding the WIC1 g2?
Please feel free to contact us directly.

Contact

Specs

Minimal start current
0,35 Ismin [1-phase]
Start current [0,25 Ismin - 3-phase]
Maintenance
25 Years
Maintenance free
For Harsh Environments
-40 / +80 °C
Temperature Range1
System Equipment
5
Integrated Test Sockets
Protection function
Ipeak>
Peak Overcurrent Protection
Robust Design
Aluminum EMC
Durable Housing
1 WIC1-1, WIC1-2 and WIC1-3. WIC1-4 -40°C / +60°C

All Device Features (Depending on variant and software function package)

Primary Application Type
Self-/CT-Powered / WIC1‑4 with optional auxiliary power supply
Mounting Type
Housing suitable for mounting plate
Inputs and Outputs
WIC1‑1 / WIC1‑2 / WIC1‑3
Current transformer inputs
3 phase currents, 1 ground current
Binary inputs
0 ... 1 only 115 VAC or 230 VAC)
Pulse Output
1 ... 2
WIC1‑4
Current transformer inputs
4
Binary inputs
0 ... 2 (supported input voltages: 24 Vdc /
48 Vdc … 60 Vdc / 110 Vdc / 110 Vac / 230 Vdc / 230 Vac)
Pulse Output
1 ... 2
Auxiliary power supply
18-300VDC, 40-250VAC
Protection and Supervision Features
Protection
ANSI Device no
IEC
Time overcurrent protection
50 / 51
I>, I>>, I>>>
Inrush blocking (2nd harmonic)
IH2
IH2
Calculated ground (earth) fault protection
50N / 51N
IG>, IG>>
Measured ground (earth) fault protection
50N / 51N
IG>, IG>> (only WIC1-4)
Ultra-fast Peak Overcurrent protection
Ipeak>
Unbalanced Load protection
46
I2/I1>
Negative-Sequence Current Protection
51Q
I2>
Thermal Overload protection
49
ThR
Switch on to Fault (SOTF)
SOTF
Cold Load Pickup (CLPU)
CLPU (only WIC1-4)
External Trip
ExP
Supervision
Circuit breaker failure
50BF
62BF (only WIC1-4)
CBF
Breaker Wear
Breaker Wear
Trip circuit monitoring
74TC
TCM
Supervision of the Station Battery
(only WIC1-4)
IG>, IG>>
Condition Monitoring
Peak Current Pointer
Peak Current Ptr
Life Load
Life Load
Recorders
ANSI Device no
IEC
Fault recorder (non-volatile)
DFR
Self-Supervision logging
(messages about device-internal
events – non-volatile)
Communication
SCADA
Modbus RTU (only WIC1-4)
Modbus TCP (only WIC1-4)

Do you have questions regarding the WIC1 g2?
Please feel free to contact us directly.

Contact

What our customers say:

The new WIC1 g2 protection relay is the successor to the successful WIC1 relays, which we started using in our Xiria, the compact Air GIS Ring Main Unit, since it’s introduction in 2002. This selfpowered relay now provides great additional options to comply with today’s digital demands.

Sezar Atakay, Front End Lead Application Engineer & Coordinator

An easy and short-term 1:1 replacement in existing projects ran absolutely smoothly, and the functionality compared to Generation 1 has also been extensively expanded.

Holger Lauer, Offer Management

The WIC1 g2 protection relay from SEG is very user-friendly, compact, and reliable.

Joerg Sandler, Master of Power Supply and Cable Networks

Downloads

WIC1 g2 Leaflet / Data-Sheet
Download
WIC1 g2 Manual
Download

Contact

Do you have questions?

Luis Miguel Faria da Graça
Sales Director

Email

Do you have questions?

Thomas Hafermann,
Senior Customer
Account Manager

Email

Do you have questions?

Brenda Brown,
Global Strategic
Account Manager, Americas

Email

Do you have questions?

Kerelos Youssef,
Customer Account Manager

Email

Do you have questions?

Jens Schürmanns,
Customer Account Manager

Email

Do you have questions?

Thomas Schütt
Customer Account Manager

Email

Do you have questions?

Ram Ravi
Customer Account Manager

Email

Do you have questions?

Massimo Citzia
Sales Support Engineer

Email

Do you have questions?

Thomas Angenvoort
Sales Support Engineer

Email

Get in
Touch

How can we assist you?

Do you have a specific project and need a quote?

Contact us directly now.

Vielen Dank für Ihre Nachricht!
Oops! Da ist etwas schief gelaufen! Lade die Seite neu.

Your Career at SEG

Would you like to become a part of the SEG Electronics family? Please check our open positions. We SEG is in the midst of an exciting transformation. We have already successfully developed the company in recent years and want to continue this positive growth. We are still SEG — but we also want to reinvent ourselves, challenge ourselves, to open up spaces and develop new concepts that make an impact.

That‘s why we are looking for great people who want to help us shape the intelligent energy supply of tomorrow. Please check our open positions, we look forward to receiving your application.

More